Exciter Model: ST9C
Following checks and corrections are applied during Validation and AutoCorrection.
- If 0.0 < Tas < 0.5*Mult*TimeStep then Tas = 0, ElseIf 0.5*Mult*TimeStep < Tas < Mult*TimeStep then Tas = Mult*TimeStep
- If 0.0 < Tr < 0.5*Mult*TimeStep then Tr = 0, ElseIf 0.5*Mult*TimeStep < Tr < Mult*TimeStep then Tr = Mult*TimeStep
- If 0.0 < Tbd < 0.5*Mult*TimeStep then Tbd = 0, ElseIf 0.5*Mult*TimeStep < Tbd < Mult*TimeStep then Tbd = Mult*TimeStep
- If Ta = 0 then Ta = Mult*TimeStep
- If KA = 0 then KA = Mult*TimeStep
- If TAUEL= 0 then TAUEL= Mult*TimeStep
- If Vrmax < Vrmin then swap the values
Mult represents the user-specified value Minimum time constant size as multiple of time step option on the Validation page of the Transient Stability Dialog
TimeStep represents the integration time step being used as described on TimeStep
Following treatment is handled during the transient numerical simulation
- If Vr > Vrmax, then Vrmax = Vr or if Vr < Vrmin, then Vrmin = Vr
Model Equations and/or Block Diagrams
Parameters:
| OEL | OEL input: if = 2, LV gate; if < 2, add to error signal |
| UEL | UEL input: if = 2, HV gate; if < 2, add to error signal |
| SCL | SCL input: if = 2, Take Over; if < 2, add to error signal |
| SW1 | Logical switch 1 (1 = Position A, 2 = Position B) |
| Tr | Filter time constant, sec. |
| Tcd | Time constant of differential part of AVR, sec. |
| Tbd | Filter time constant of differential part of AVR, sec. |
| Za | Dead-band for differential part influence on AVR, sec. |
| Ka | AVR gain |
| Ku | Gain associated with activation of takeover UEL |
| Ta | Time constant of AVR, sec. |
| Tauel | Time coonstant of underexcitation limiter, sec. |
| Vrmax | Maximum regulator output, p.u. |
| Vrmin | Minimum regulator output, p.u. |
| Kas | Power converter gain, proportional to supply voltage, p.u. |
| Tas | Equivalent time constant of power converter firing control, sec. |
| Kp | Potential circuit voltage gain coefficient |
| ThetaPDeg | Potential circuit phase angle, degrees |
| Ki | Potential circuit current gain coefficient |
| Xl | Reactance associated with compound source, p.u. |
| Kc | Rectifier loading factor proportional to commutating reactance |
| VbMax | Maximum limit on exciter voltage based on supply condition, p.u. |